D1 · T5, ELECTRICAL7% of the exam

Panelboard Defects, Subpanels and Problem Panels

Lesson 24C of 116. Free to read, no account and no card. The rest of the course is $225.

Multiple conductors in one lug

A lug is a terminal that clamps a conductor to a bus, a circuit breaker, or a terminal bar. A lug is usually listed for a single conductor. More conductors in a lug than the device allows is a common enclosure defect. On a circuit breaker, it is sometimes called a double tap.

The device manufacturer's instructions set how many conductors a lug may hold. The general rules are:

  • Energized and neutral conductors: one conductor per lug.
  • Equipment grounding conductors (EGCs): two per lug, if both are the same size.

Instructions on the panelboard label override the general rules. A lug not designed for more than one conductor may let a conductor slip out.

The most common exception is a group of Square D circuit breakers rated 15, 20, and 30 amps, some sold under the Homeline brand. A double saddle on these breakers sits beneath the lug screw and holds two conductors if they are the same size.

An overcurrent protection device (OPD) may fail to protect multiple conductors in one lug, or the conductors may be overfused. Multiple conductors in one lug can be especially dangerous.

The same rules apply at terminal bars. Doubled neutral conductors in one lug are not allowed. Two EGCs in one lug are allowed if they are the same gauge.

Copper and aluminum conductors in the same lug can corrode. A lug with anti-oxidant paste can look good. A deteriorated lug is a defect.

Other typical defects inside enclosures

  1. Rust: rust indicates that water may be leaking into the enclosure. It could raise resistance and start an electrical fire. Moderate rust is reportable, and so is significant rust, including rust on a dead front cover.
  2. Bus bar deterioration: a deteriorated bus bar is a typical defect inside an enclosure.
  3. Contaminants in the enclosure, such as paint and drywall joint compound: these could also raise resistance and start an electrical fire.
  4. Damaged conductors and insulation: the conductor and its insulation should be undamaged. Nicks in a conductor or its insulation, and missing strands on a multi-strand conductor, should be trimmed back to undamaged material or replaced. All strands of a multi-strand conductor should be inside the lug.
  5. Melted insulation and charred conductors: these indicate a loose lug connection, or an overcurrent the OPD did not interrupt.
  6. Excess uninsulated conductor at the lug of a circuit breaker: bare conductor should not extend beyond the circuit breaker case. Exposed conductor past the case creates a possible electric shock hazard.
  7. Conductors not inserted straight into lugs: a conductor should be substantially straight where it enters a lug. A substantially skewed conductor may not be securely fastened. A sharp bend at the lug can also make the conductor appear reduced in size.
  8. Pointed screws used to secure enclosure covers: the point could pierce the insulation on a conductor and energize the enclosure. Tape is not an acceptable repair for the damaged conductor.
  9. Branch circuits not labeled: each branch circuit should have a permanent label with enough detail to tell it apart from the other circuits. A label based on how the current occupant uses a room is not acceptable.
  10. Neutral conductors that are energized but not marked as such: a neutral conductor may serve as an energized conductor. It must carry a permanent mark at every accessible point and inside the enclosure, usually black marker or electrical tape.
  11. Circuit breaker manufacturer different from panelboard manufacturer: panelboards and breakers are designed to work together. A breaker made by another manufacturer may not be installed, even where it appears to fit. Certain models may be interchanged between manufacturers. Determining which ones is outside the scope of a home inspection. The home inspector should recommend evaluation by an electrician.
  12. Handle ties absent or improper on 240 volt or multiwire branch circuit breakers: these circuits must disconnect both conductors at the same time, using an approved handle tie between the breaker handles. Wire, nails, and other improvised ties are not permitted.
  13. Absent tabs and knockouts: a knockout is a removable disc in the enclosure wall for a cable or conduit entry. A tab is a removable piece in the dead front cover at a breaker space. An open tab or knockout is an electrical shock hazard. Tape, cardboard, and other makeshift fillers are not permitted. Replacement material must be similar to the original.
  14. Low voltage components inside the enclosure and conduit: door bell transformers, telephone cable, coaxial cable, and other low voltage components may not share an enclosure or conduit with high voltage components, unless non-conductive guards physically separate the two.
  15. Too many circuit breakers on panelboard, or half-height circuit breakers in wrong slots: both limits appear on the panelboard label, which gives the maximum number of branch circuits and which slots, if any, accept half-height breakers.
  16. Panelboard ampacity greater than the ampacity of the service entrance or feeder conductors: a minimum ampacity for the supply conductors is printed on the panelboard label. Supply conductors may exceed this minimum, but may not fall below it.
  17. Cables and conduit that are not secured to the enclosure: a cable should enter the enclosure inside conduit or through a cable clamp. Metal conduit should be joined to the enclosure by a metal fitting. Without one, the installer should add a bonding jumper.
  18. Fused neutral: an OPD should not be connected to a neutral conductor. In the rare case that the OPD opens the neutral, current stops but the circuit remains energized. The defect is usually limited to very old electrical systems.
  19. Damaged enclosure: an enclosure should be intact, free from physical damage, and have all manufacturer approved parts installed. Covers and doors should open at least 90 degrees without binding, for safe access inside. A cover that a wall prevents from opening does not open at least 90 degrees.

Standards: IRC 2018 sections cover NM cable ampacity (E3705.4.4), branch circuit conductor ampacity (Table E3705.1), panelboard ampacity rating, circuit identification, and one neutral per lug (E3706), AFCI and GFCI locations (E3902), and general cabinet and panelboard installation (E3907).

Subpanel grounding and bonding

Why subpanel grounding is different

IRC 2018 Section E3607.2 (NEC 2017 Article 250.24(A)(1)) prohibits connecting a grounded (neutral) conductor to ground anywhere downstream of the service disconnecting means. Section E3607.3.2 provides the exception. Past the service equipment, neutral conductors must stay isolated from EGCs and from all other bonded metal.

This rule exists because the neutral conductor carries current. Under normal conditions it is at zero voltage and is not a shock risk. Reversed polarity, at a receptacle or inside a lamp or similar device, could energize the neutral. A ground fault in improperly bonded metal is a similar risk. Either way, metal bonded to the EGCs could become energized and shock anyone who touches it.

A neutral grounded at a distribution panelboard creates parallel return paths for current. The condition of those paths is unknown.

Subpanels

For grounding and bonding, a subpanel is any panelboard downstream of the service equipment. This includes a main panelboard of the main lug type. Appliances, appliance disconnects, junction boxes, and outlets are included too.

Terminal bars in a subpanel

  • Neutral conductors should land on their own neutral terminal bar or lugs, isolated from both the EGCs and the enclosure.
  • EGCs should not connect to the neutral terminal bar. The neutral terminal bar should not connect to the enclosure.
  • EGCs should connect to a separate grounding terminal bar, which should be bonded to the subpanel enclosure.

The two most common bonding methods are mounting the grounding bar directly on the enclosure and connecting it with a bar or strap.

Detached buildings

A detached building includes a barn, a storage shed, a work shed, or a guest house supplied with electricity from the main house.

A single branch circuit of 15 or 20 amps serves many detached buildings. That arrangement needs no special grounding or bonding connections if the circuit has an EGC, which it should.

Two or more branch circuits, or a feeder to a subpanel, require a grounding electrode system at the detached building.

New work. New branch circuits and feeders to a detached building should include an EGC, connected to the grounding electrode. Neutral conductors should remain isolated from both the EGC and the subpanel enclosure. The feeder to the detached building is a four wire feeder: two ungrounded (hot) wires, one grounded (neutral) wire, and one equipment grounding (bonding) wire.

Existing work without an EGC. An existing circuit or feeder to a detached building that has no EGC may remain. If no grounding electrode is present, one should be installed. The subpanel there should be set up as a main breaker panel. EGCs and neutral conductors may then share terminal bars. Both should be bonded to the enclosure and connected to the grounding electrode.

Typical defects, subpanels

Home inspectors should report these subpanel defects:

  1. EGCs and neutral conductors on the same terminal bar: this includes an EGC and a neutral joined in a wire nut inside the enclosure.
  2. EGCs or EGC terminal bar not bonded to enclosure: this includes an absent bonding jumper between the grounding bar and the enclosure.
  3. Other typical defects inside enclosures: every item on that list also applies to subpanels.

Standards: IRC 2018 sections cover the GEC connection location (E3607.2) and grounding in detached buildings (E3607.3).

Potential problem panelboards

A few older panelboards have known or suspected problems. Home inspectors should look for them and make recommendations when one is found. Online sources describe them, and some home inspectors direct clients to those sources. Some electricians do not know of these alleged problems.

Most of these panelboards have reached or exceeded their expected service life. This end of life condition should be reported in addition to any brand specific defects.

Three potential problems are alleged across these brands:

  • circuit breakers that do not trip when they should
  • circuit breakers that are energized while showing deenergized
  • arcing at the circuit breaker to busbar connection, not visible unless the breaker is removed

Federal Pacific Stab-Lok

Federal Pacific Stab-Lok panelboards sometimes carry the FPE logo on the enclosure. Other names for them are Federal Electric and Challenger. They appear most often in houses built from the mid-1950s to the early 1980s. The alleged design defects involve the circuit breakers, the panelboard, and the enclosure. All three potential problems are alleged.

On these panelboards, removing the dead front can be difficult, and breakers may fall out as it comes off. Some home inspectors do not remove these covers.

A substantial majority of experienced home inspectors report the panelboard, describe its potential risks, and recommend that a qualified electrician evaluate it. Because some electricians do not know of the alleged problems, some home inspectors recommend replacement.

Only Stab-Lok panelboards are involved. The alleged defects do not apply to other Federal Pacific panelboards.

Zinsco and Zinsco-Sylvania

Zinsco panelboards, also sold as Zinsco-Sylvania, appear most often in houses built from the 1940s to the 1970s. The alleged design defects involve the circuit breakers and the panelboard. All three potential problems are alleged. A majority of experienced home inspectors report the panelboard, describe its potential risks, and recommend that a qualified electrician evaluate it.

Bulldog Pushmatic

Bulldog Pushmatic panelboards are found mostly in houses from the 1950s and 1960s, and may be found in houses built up to the 1990s. The alleged design defects involve the circuit breakers, especially those from the 1950s and 1960s. Two problems are alleged: breakers that do not trip when they should, and breakers energized while showing deenergized.

Experienced home inspectors are split on these panelboards. Some believe the evidence is insufficient to warrant reporting these panelboards. Others report 1950s and 1960s panelboards for two reasons: advanced age, and listed replacement parts that may be hard to find and may be costly. These home inspectors report the panelboard, describe its potential risks, and recommend that a qualified electrician evaluate it.

Numbers and Rules to Memorize

ItemValue
Energized or neutral conductors per lugOne, as the general rule
EGCs per lugTwo, if the same size, as the general rule
What sets the conductor count for a lugThe device manufacturer's instructions; the panelboard label overrides the general rules
Most common exceptionSome Square D 15, 20, and 30 amp breakers (Homeline) with a double saddle
Multiple conductors in one lugCan be especially dangerous: no OPD, or an overfused one
Copper and aluminum in one lugCan corrode
Rust, paint, or joint compound in an enclosureCould raise resistance and start an electrical fire
Nicked conductors or missing strandsTrim back to undamaged material, or replace
Melted insulation, charred conductorsLoose lug connection, or an overcurrent the OPD did not interrupt
Bare conductor past the breaker casePossible electric shock hazard
Conductor entering a lugSubstantially straight
Pointed cover screwsCould pierce insulation and energize the enclosure; tape is not an acceptable repair
Circuit labelsPermanent and distinct; occupant specific room uses are not acceptable
Neutral used as an energized conductorPermanent mark at every accessible point and in the enclosure
Breaker from another manufacturerMay not be installed; substitution is out of scope; recommend an electrician
240 volt and multiwire breakersApproved handle ties only
Tabs and knockoutsReplace with similar material; no tape or cardboard
Low voltage in a high voltage enclosure or conduitNot allowed without non-conductive guards
On the panelboard labelBranch circuit count, half-height slots, minimum supply conductor ampacity
Supply conductorsMay exceed the label minimum, not fall below it
Cable at an enclosureCable clamp, or inside conduit
Metal conduit at an enclosureMetal fitting; otherwise a bonding jumper
Fused neutralDefect; usually only in very old systems
Enclosure covers and doorsOpen at least 90 degrees
Code sections for enclosuresIRC 2018 E3705.4.4, Table E3705.1, E3706, E3902, E3907
Neutral isolation past the service disconnectIRC 2018 E3607.2 (NEC 2017 250.24(A)(1)); exception E3607.3.2
Subpanel neutral terminal barIsolated from EGCs and the enclosure
Subpanel grounding terminal barBonded to the enclosure
Detached building, one 15 or 20 amp circuitNo special grounding if the circuit has an EGC
Detached building, two or more circuits or a feederGrounding electrode system required
Existing circuit or feeder with no EGCMay remain; add an electrode if absent; set up the subpanel as a main breaker panel
Subpanel standardsIRC 2018 E3607.2, E3607.3
Federal Pacific Stab-LokMid-1950s to early 1980s; breakers, panelboard, enclosure; substantial majority report it
Zinsco1940s to 1970s; breakers and panelboard; majority report it
Bulldog Pushmatic1950s and 1960s, found up to the 1990s; breakers only; opinion split
Key terms17

Every term this part of the manual defines, plus the ones the lesson introduces. The exam uses them exactly as defined.

Anti-oxidant paste
a compound applied to a conductor at a lug to limit corrosion.
Detached building
a structure apart from the house, such as a storage shed, a work shed, a barn, or a guest house whose electricity comes from the main house.
Double saddle
a fitting under the lug screw of some Square D breakers that holds two same-size conductors.
Double tap
two or more conductors in one circuit breaker lug.
Equipment grounding conductor (EGC)
a conductor that connects metal parts to the grounding system.
Grounding electrode conductor (GEC)
the conductor that connects the grounding system to the grounding electrode.
Grounding electrode system
the connection between a building's grounding system and the earth.
Grounding terminal bar
the bar where EGCs connect. In a subpanel it is bonded to the enclosure.
Handle tie
an approved device that joins two breaker handles so both conductors of a circuit disconnect together.
Knockout
a removable disc in an enclosure wall, taken out for a cable or conduit entry.
Lug
a terminal that clamps a conductor to a bus, a breaker, or a terminal bar.
Main lug panelboard
a panelboard without a main breaker. Its disconnecting means is upstream.
Neutral terminal bar
the bar where neutral conductors connect. In a subpanel it is isolated from the EGCs and the enclosure.
Overcurrent protection device (OPD)
a circuit breaker or fuse that interrupts current above its rating.
Parallel return path
a second path for return current, created by a neutral to ground connection downstream of the service equipment.
Subpanel
for grounding and bonding, any panelboard downstream of the service equipment.
Tab
a removable piece in the dead front cover that closes an unused breaker space.

Check on learning

20 questions from the bank, on this lesson only. Eighty percent is the line. Nothing is revealed until you submit, because an answer you can see before you commit teaches you nothing about whether you knew it.

  1. 1Two conductors landed under the lug of a single circuit breaker are sometimes called:
  2. 2Under the general rule, how many energized or neutral conductors may be landed in one lug?
  3. 3Two equipment grounding conductors may share one lug under which condition?
  4. 4Which breakers does the manual name as the MOST common exception to the one conductor per lug rule?
  5. 5Rust inside an electrical enclosure is an indication of:
  6. 6Melted insulation and charred conductors at a breaker lug indicate:
  7. 7Screws with pointed tips used to secure an enclosure cover create which hazard?
  8. 8Which method of identifying a branch circuit does the manual call unacceptable?
  9. 9A neutral conductor put to use as an energized conductor must be:
  10. 10A home inspector finds circuit breakers made by a company other than the panelboard maker. What is the appropriate action?
  11. 11Which materials are permitted as handle ties on a pair of 240 volt circuit breakers?
  12. 12An absent tab or knockout in a panelboard enclosure is replaced with:
  13. 13Low voltage components may share an enclosure with high voltage components under which condition?
  14. 14The panelboard label names a smallest allowable ampacity for the conductors supplying it. Those conductors may be:
  15. 15Why is an overcurrent device installed on a neutral conductor a defect?
  16. 16Enclosure covers and doors are expected to move freely and swing AT LEAST:
  17. 17For grounding and bonding purposes, which panelboard is treated as a subpanel?
  18. 18Inside a subpanel, how are the neutral terminal bar and the grounding terminal bar treated?
  19. 19A detached building requires a grounding electrode system of its own once it is served by:
  20. 20Most Federal Pacific Stab-Lok panelboards went into houses built:
20 unanswered